MOQ : 12
Kontrol Voltajı: 3-32VDC
Kontrol Akımı: 5-25mma
Yük Voltajı: 120: 60-1200VAC
Yük akımı: 500A, 600A, 800A, 1000a
Durum Üstü Voltaj Düşüşü: AC < 1.6VAC
OF-OF-OFF Saati: AC≤10ms
Durum dışı sızıntı akımı AC≤10mA
Dielektrik dayanma voltajı: ≥2500vac
Ortam sıcaklığı: -30 ~ 80 ℃
Boyutlar: 500-600A: 115 × 53 × 60mm
800A: 125 × 63 × 70mm
1000A: 149 × 66 × 76mm
Kurulum Formu: Cıvata Kurulumu
Açıklama: 5A'nın üzerindeki yükler bir radyatörle donatılmalıdır
80A'nın üzerindeki yükler fan zorla soğutma veya su soğutma ile donatılmalıdır
| HHG1K Serisi | |
| Model | HHG1K-1/032F-120 (SSR-DA) |
| Kontrol voltajı | 3-32VDC |
| Kontrol akımı | 5-25mma |
| Yük voltajı | 120: 60-1200VAC |
| Yük akımı | 500a, 600a, 800a, 1000a |
| Durum üzerindeki voltaj düşüşü | AC ≤ 1.6VAC |
| ON-OFF Saati | AC≤ 10ms |
| Devlet dışı sızıntı akımı | AC ≤ 10mA |
| Dielektrik mukavemet | ≥ 2500VAC |
| Ortam sıcaklığı. | -30 ~ 80 ° C |
| Boyut | 500-600A : 115 × 53 × 60mm 800A : 125 × 63 × 70mm 1000A : 149 × 66 × 76mm |
| Kurulum formu | Cıvata kurulumu |
| Talimat | 5A'nın üzerindeki yükler için bir radyatör takılmalıdır; 80A'nın üzerindeki yükler için güçlü bir soğutma veya su soğutma fanı eklenmelidir |
Q1. How much current margin is recommended when selecting a 500–1000A SSR?
Do not select at the load current. Add margin for inrush, ambient temperature and heat-sink quality, and a larger margin still for inductive loads. Resistive heaters need less margin than transformers or motors. Send the load, supply voltage and cabinet temperature, and our engineers will suggest a model.
Q2. Does a 1000A solid state relay need short-circuit protection?
Yes. An SSR is not short-circuit proof, and a fault current can destroy the output stage before an ordinary breaker trips. Use a fast-acting semiconductor fuse coordinated with the relay’s I²t withstand. Ask us for the I²t data for the chosen model when requesting a quote.
Q3. With ≤10mA off-state leakage, is the load truly de-energized?
No. An SSR is not an isolating device. Leakage of up to 10mA can keep small loads faintly energized, and the output remains connected to the line. For maintenance, use an upstream disconnect or contactor as well. This also matters for loads sensitive to small leakage currents.
Q4. Can the HHG1K be used on three-phase 380V, 480V or 690V systems?
The load voltage range is 60–1200VAC, which covers common three-phase supplies with headroom for transients. A three-phase heater bank typically uses one relay per controlled phase, depending on wiring. Tell us the supply voltage and connection, star or delta, and we will confirm the arrangement.
Q5. How is the correct HHG1K rating determined for heating control cabinets?
Send the heater power in kW, supply voltage, number of phases and cooling method. We will calculate the load current and suggest 500A, 600A, 800A or 1000A. The MOQ is 12 pcs, so single cabinets and project batches are both possible.
Bittik 34 bu sektörde yılların deneyimini oluşturdu ve bir