Specification | HHS5 | HHS5G | HHS5C | HHS5F | HHS5F1 | HHS5F2 | HHS5F3 | HHS5R |
Movement Forms | Power-on delay | Release delay | Power-on delay with momentary contact | Power failure delay | Cyclic delay | |||
Delay Range | A:0.05s~0.5s/5s/30s/3m B:0.1s-1s/10s/60s/6m C:0.5s-5 /50s/5m/30m D:1s-10s/100s/10m/60m E:5s-60s/10m/60m/6h F:0.25m~2m/20m/2h/12h G:0.5m~4m/40m/4h/24h | 0.1s-1s;0.2s-2s 0.5s-5s;1s-10s;2.5s-30s;5s-60s;10s-120s;15s-180s | 60s-600s 180s-1800s 360s-3600s | 0.5s~6s/60s1s~10s/10m2.5s~30s/30m5s~60s/60m | ||||
Setting method | Potentiometer | |||||||
Repetition error | Er<1% when the delay range is greater than 1s; Dr<50ms when the delay range is less than 1s. | Er<5% when the delay range is greater than 1s; Dr<100ms when the delay range is less than 1s. | Er<1% when the delay range is greater than 1s; Dr<50ms when the delay range is less than 1s. | |||||
Number of contacts | Delay 2 conversion | Delay 1 conversion Momentary 1-conversion | Delay 1conversion | Delay 2 conversion | Delay 1 conversion Momentary 1-conversion | Delay 1conversion | ||
Contact capacity | 3A AC250V (resistive) | |||||||
Operating power | AC380V,AC220V,AC110V,AC36V,AC24V, 50Hz;DC24V,DC110V,DC220V | AC110V,AC220V 5Hz;DC24V,(85%-110%)Ue | ||||||
Temperature range | -5°-40°C | |||||||
Altitude | ≤2000m | |||||||
Humidity | The relative humidity of the air is <50% at a maximum temperature of 40°C at the installation site, higher relative humidity may be permitted at lower temperatures, e.g. up to 90% at 20°C. Special measures should be taken for occasional condensation due to temperature changes. | |||||||
Installation | Unit, panel and 35m rail mounting with different sockets and accessories. | |||||||
Conventional heating current Ith | 5A | |||||||
Rated insulation voltage Ui | 400V | |||||||
Rated impulse withstand voltage Uimp | 2.5KV | |||||||
Ue/Ie | Rated Working Voltage Ue/Rated Working Current Ie:AC-15 Ue:AC250V,Ie:3A in each category of use. |
HHS5F
HHS5 series time relays are suitable for use as time-delay elements in control circuits with AC 50Hz, operating voltages of 380V and below, or DC operating voltages of 24V, to connect or break circuits at preset times.
This series of relays has the advantages of small size, light weight, high precision, wide delay range, good performance and so on, which is widely used in automation control circuits for delay control.
This product meets the relevant requirements of GB/T 14048.5.
Wiring Diagram
Specification-HHS5F
Rated Supply Voltage | AC24V、AC36V、ACI10V、AC220V、 AC380V50Hz:DC24V、DCI10V、 DC220V:Allowable voltage fluctuation range (85%~110%)Ue |
Time Delay range | 1s、5s、10s、30s、60s、120s、180s |
Repetition error | ≤5% |
Contact | One set of delay contacts with reset |
Rated Load of the Contact | 3A AC250V(Resistive) |
Dimensions | 40.5×54×84mm |
Installation | Panel and 35mm rail mounting with different sockets and accessories. |
Temperature | -5℃ to 40℃ |
Operating mode | Power off delay |
HHS5F1
HHS5 series time relays are suitable for use as time-delay elements in control circuits with AC 50Hz, operating voltages of 380V and below, or DC operating voltages of 24V, to connect or break circuits at preset times.
This series of relays has the advantages of small size, light weight, high precision, wide delay range, good performance and so on, which is widely used in automation control circuits for delay control.
This product meets the relevant requirements of GB/T 14048.5.
Wiring Diagram
Specification-HHS5F1
Rated Supply Voltage | AC24V、AC36V、ACl10V、AC220V、 AC380V50Hz:DC24V、DCI10V、 DC220V:Allowable voltage fluctuation range (85%~110%)Ue |
Time Delay Range | 1s、5s、10s、30s、60s、120s、180s |
Repetition Error | ≤5% |
Contact | 2C time delay |
Rated Load of the Contact | 3A AC250V(Resistive) |
Dimensions | 40.5×54×84mm |
Installation | Panel and 35mm rail mounting with different sockets and accessories. |
Temperature | -5℃ to 40℃ |
Operating Mode | Power off delay |
HHS5PA
HHS5 series time relays are suitable for use as time-delay elements in control circuits with AC 50Hz, operating voltages of 380V and below, or DC operating voltages of 24V, to connect or break circuits at preset times.
This series of relays has the advantages of small size, light weight, high precision, wide delay range, good performance and so on, which is widely used in automation control circuits for delay control.
This product meets the relevant requirements of GB/T 14048.5.
Specification-HHS5PA
Rated Supply Voltage | AC24V、AC36V、ACl10V、AC220V、 AC380V50Hz:DC24V、DCI10V、 DC220V:Allowable voltage fluctuation range (85%~110%)Ue |
Time Delay range | 0.1s-9.9s、1s-99s、0.1m-9.9m、1m-99m、 0.1h-9.9h、1h-99h |
Repetition error | Er<1%when the delay range is greater than 1s;Dr<50ms when the delay range is less than 1s |
Contact | A.Delay 2 convert B.Delay 1 convert,instantaneous 1 convert |
Rated Load of the Contact | 3A AC250V(Resistive) |
Dimensions | 40.5×54×75.5mm |
Installation | Panel and 35mm rail mounting with different sockets and accessories. |
Temperature | -5℃ to 40℃ |
Operating mode | Power off delay |