< Back
Specification HHS5 HHS5G HHS5C HHS5F HHS5F1 HHS5F2 HHS5F3 HHS5R
Movement Forms Power-on delay Release delay Power-on delay with momentary contact Power failure delay Cyclic delay
Delay Range A:0.05s~0.5s/5s/30s/3m
B:0.1s-1s/10s/60s/6m
C:0.5s-5 /50s/5m/30m
D:1s-10s/100s/10m/60m
E:5s-60s/10m/60m/6h
F:0.25m~2m/20m/2h/12h
G:0.5m~4m/40m/4h/24h
0.1s-1s;0.2s-2s
0.5s-5s;1s-10s;2.5s-30s;5s-60s;10s-120s;15s-180s
60s-600s
180s-1800s
360s-3600s
0.5s~6s/60s1s~10s/10m2.5s~30s/30m5s~60s/60m
Setting method Potentiometer
Repetition error Er<1% when the delay range is greater than 1s; Dr<50ms when the delay range is less than 1s. Er<5% when the delay range is greater than 1s; Dr<100ms when the delay range is less than 1s. Er<1% when the delay range is greater than 1s; Dr<50ms when the delay range is less than 1s.
Number of contacts Delay 2 conversion Delay 1 conversion
Momentary 1-conversion
Delay 1conversion Delay 2 conversion Delay 1 conversion
Momentary 1-conversion
Delay 1conversion
Contact capacity 3A AC250V (resistive)
Operating power AC380V,AC220V,AC110V,AC36V,AC24V, 50Hz;DC24V,DC110V,DC220V AC110V,AC220V 5Hz;DC24V,(85%-110%)Ue
Temperature range  -5°-40°C
Altitude ≤2000m
Humidity The relative humidity of the air is <50% at a maximum temperature of 40°C at the installation site, higher relative humidity may be permitted at lower temperatures, e.g. up to 90% at 20°C. Special measures should be taken for occasional condensation due to temperature changes.
Installation Unit, panel and 35m rail mounting with different sockets and accessories.
Conventional heating current Ith 5A
Rated insulation voltage Ui 400V
Rated impulse withstand voltage Uimp 2.5KV
Ue/Ie Rated Working Voltage Ue/Rated Working Current Ie:AC-15 Ue:AC250V,Ie:3A in each category of use.

 

HHS5F

HHS5 series time relays are suitable for use as time-delay elements in control circuits with AC 50Hz, operating voltages of 380V and below, or DC operating voltages of 24V, to connect or break circuits at preset times.

This series of relays has the advantages of small size, light weight, high precision, wide delay range, good performance and so on, which is widely used in automation control circuits for delay control.

This product meets the relevant requirements of GB/T 14048.5.

 

Wiring Diagram

Specification-HHS5F

Rated Supply Voltage AC24V、AC36V、ACI10V、AC220V、
AC380V50Hz:DC24V、DCI10V、
DC220V:Allowable voltage fluctuation range
(85%~110%)Ue
Time Delay range 1s、5s、10s、30s、60s、120s、180s
Repetition error ≤5%
Contact One set of delay contacts with reset
Rated Load of the
Contact
3A AC250V(Resistive)
Dimensions 40.5×54×84mm
Installation Panel and 35mm rail mounting with
different sockets and accessories.
Temperature -5℃ to 40℃
Operating mode Power off delay

 

HHS5F1

HHS5 series time relays are suitable for use as time-delay elements in control circuits with AC 50Hz, operating voltages of 380V and below, or DC operating voltages of 24V, to connect or break circuits at preset times.

This series of relays has the advantages of small size, light weight, high precision, wide delay range, good performance and so on, which is widely used in automation control circuits for delay control.

This product meets the relevant requirements of GB/T 14048.5.

 

Wiring Diagram

 

Specification-HHS5F1

Rated Supply Voltage AC24V、AC36V、ACl10V、AC220V、
AC380V50Hz:DC24V、DCI10V、
DC220V:Allowable voltage fluctuation range
(85%~110%)Ue
Time Delay Range 1s、5s、10s、30s、60s、120s、180s
Repetition Error ≤5%
Contact 2C time delay
Rated Load of the
Contact
3A AC250V(Resistive)
Dimensions 40.5×54×84mm
Installation Panel and 35mm rail mounting with
different sockets and accessories.
Temperature -5℃ to 40℃
Operating Mode Power off delay

 

HHS5PA

HHS5 series time relays are suitable for use as time-delay elements in control circuits with AC 50Hz, operating voltages of 380V and below, or DC operating voltages of 24V, to connect or break circuits at preset times.

This series of relays has the advantages of small size, light weight, high precision, wide delay range, good performance and so on, which is widely used in automation control circuits for delay control.

This product meets the relevant requirements of GB/T 14048.5.

 

Specification-HHS5PA

Rated Supply Voltage AC24V、AC36V、ACl10V、AC220V、
AC380V50Hz:DC24V、DCI10V、
DC220V:Allowable voltage fluctuation range
(85%~110%)Ue
Time Delay range 0.1s-9.9s、1s-99s、0.1m-9.9m、1m-99m、
0.1h-9.9h、1h-99h
Repetition error Er<1%when the delay range is greater than
1s;Dr<50ms when the delay range is less
than 1s
Contact A.Delay 2 convert
B.Delay 1 convert,instantaneous 1 convert
Rated Load of the
Contact
3A AC250V(Resistive)
Dimensions 40.5×54×75.5mm
Installation Panel and 35mm rail mounting with
different sockets and accessories.
Temperature -5℃ to 40℃
Operating mode Power off delay

 

Related Product

We has over 34 years of experience in this industry and has built a
reputation for providing quality products and services at competitive prices.

Tell Us Your Requirements Questions Needs Ideas Plans