< Back

Intelligent Temperature Itinerant Detector HD Series

HD series
Model HD-C800-0821 HD-C800-0822 HD-C800-0821-C4 HD-C800-0822-C4
Module (1~8 temperature display channels can be set,
with two sets of alarm relays, without RS485 module)
(with RS485 module)
Measurement signal Thermocouple: K, E Thermal resistance: Pt100, Cu50 Thermocouple: K, E Thermal resistance: Pt100, Cu50
Itinerant detecting point circuit 1~8 circuit
Itinerant detecting method Automatic and manual
Itinerant detecting time Automatic itinerant detecting time 0-100s
Alarm mode Upper limit alarm, lower limit alarm
Alarm output Relay contact (control hysteresis adjustable)
Contact capacity Passive AC 220V 3A (resistive load)
Comm. interface RS485 (optional)
Supply voltage AC 220V
Dimension 160×80×103.5mm
Hole size 152×76mm
Installation method Panel type
Typical application Multi-point temperature monitoring for grain depots, switchgear assemblies, motor protection places etc.

Related Product

We has over 34 years of experience in this industry and has built a
reputation for providing quality products and services at competitive prices.

Tell Us Your Requirements Questions Needs Ideas Plans